HVAC ACH Calculator
Two calculations in one: find the air changes per hour a room is actually getting from its measured airflow, or work backwards to the CFM you need to hit a target ACH. Enter length × width × height, floor area × ceiling height, or a known volume — imperial or metric. Free, no signup.
ASHRAE 170 specifies healthcare spaces as both a minimum total ACH and a minimum outdoor ACH — an operating room is 20 total with 4 outdoor, i.e. 20% outdoor air.
Air changes per hour
6.00
1,680 ft³ · Living / family room target 6–8 ACH
ACH assumes the room mixes perfectly. It is a sizing and screening metric — ASHRAE 62.1 sizes commercial outdoor air per person and per square foot, and 62.2 sizes homes from floor area and bedroom count. Check the governing code before you commit to equipment.
Residential
- Whole house (ventilation minimum)
- 0.35–0.6 ACH
- Living / family room
- 6–8 ACH
- Bedroom
- 5–6 ACH
- Bathroom
- 6–7 ACH
- Residential kitchen
- 7–8 ACH
- Laundry room
- 8–9 ACH
- Basement
- 3–4 ACH
- Attached / parking garage
- 4–6 ACH
Commercial
- Business office
- 6–8 ACH
- Conference room
- 8–12 ACH
- Hallway / corridor
- 3–5 ACH
- Classroom
- 6–20 ACH
- Retail store / mall
- 6–10 ACH
- Restaurant dining area
- 8–10 ACH
- Commercial kitchen
- 14–60 ACH
- Bar / tavern
- 15–20 ACH
- Gym / fitness room
- 6–10 ACH
- Public restroom
- 10–12 ACH
- Theatre / auditorium
- 8–15 ACH
- Indoor swimming pool
- 10–15 ACH
- Smoking lounge
- 15–20 ACH
- Server / computer room
- 10–20 ACH
Industrial
- Warehouse
- 6–30 ACH
- Machine shop
- 6–12 ACH
- Welding shop
- 10–20 ACH
- Repair garage
- 20–30 ACH
- Boiler / mechanical room
- 15–20 ACH
- Paint / spray booth
- 20–50 ACH
- Bakery / food production
- 20–30 ACH
Healthcare
- Hospital patient room
- 6–8 ACH
- Airborne isolation room (AII)
- 12–15 ACH
- Operating room
- 20–25 ACH
- Cleanroom (ISO 7)
- 60–90 ACH
Engineering Toolbox / Omni residential table — conditioned-air turnover, not outdoor air.
- Air changes per hour
- ACH = CFM × 60 ÷ ft³
- Required airflow
- CFM = ACH × ft³ ÷ 60
- Whole house (ASHRAE 62.2)
- 0.35 ACH minimum
- Patient room (ASHRAE 170)
- 6 ACH total, 2 outdoor
- Isolation room (ASHRAE 170)
- 12 ACH total, negative
- Operating room (ASHRAE 170)
- 20 ACH total, 4 outdoor
- Enclosed garage (IMC §404)
- 0.75 CFM/ft² ≈ 4.5 ACH
- Residential supply rule of thumb
- ≈ 1 CFM per sq ft
Pick the direction
Find ACH turns measured airflow and room volume into air changes per hour. Find required CFM starts from a target ACH and tells you the airflow to deliver.
Describe the room
Enter the three dimensions, the floor area plus ceiling height, or a volume straight off your takeoff. Choose the space type so the result is graded against the right range.
Read the verdict
See ACH or required CFM, minutes per air change, airflow per square foot, and the recommended CFM window for that room — plus an optional outdoor-air split for ASHRAE 170 work.
How it works
- 1
Pick the direction
Find ACH turns measured airflow and room volume into air changes per hour. Find required CFM starts from a target ACH and tells you the airflow to deliver.
- 2
Describe the room
Enter the three dimensions, the floor area plus ceiling height, or a volume straight off your takeoff. Choose the space type so the result is graded against the right range.
- 3
Read the verdict
See ACH or required CFM, minutes per air change, airflow per square foot, and the recommended CFM window for that room — plus an optional outdoor-air split for ASHRAE 170 work.
How to calculate air changes per hour
Air changes per hour is one identity and its inverse. To find ACH, multiply airflow in CFM by 60 to get cubic feet of air moved per hour, then divide by the room volume in cubic feet: ACH = (CFM × 60) ÷ volume. A 12 ft × 14 ft × 10 ft room is 1,680 cubic feet, so 168 CFM moves 10,080 cubic feet per hour and delivers exactly 6 air changes. Flip it around when you are sizing equipment: CFM = (ACH × volume) ÷ 60, so the same room at a 6 ACH target needs 168 CFM of supply or exhaust.
The number only means something against a target. Residential living spaces are typically designed for 6–8 ACH and bedrooms for 5–6, while a commercial kitchen runs 14–60 and a repair garage 20–30 because the load is contaminant dilution rather than comfort. Healthcare is code-driven: ASHRAE 170 sets a minimum of 6 total air changes for a patient room, 12 for an airborne infection isolation room, and 20 for an operating room, each with a minimum outdoor-air share. ACH assumes perfect mixing and is a screening and sizing metric — ASHRAE 62.1 sizes commercial outdoor air per person and per square foot, and 62.2 sizes homes from floor area and bedroom count, so confirm against the governing code before you commit to equipment.
Related tools
More free resources to help you price jobs, stay organized, and capture leads.
Business Templates
Free invoices, estimates, and work orders for your trade.
Browse templatesAI Receptionist
Let Larry answer every call while you focus on the job.
Learn moreContractor Blog
Guides on pricing, hiring, marketing, and operations.
Read guidesHVAC Licensing
State licensing requirements, exams, and renewal rules for hvac contractors.
View statesACH Calculator (Air Changes Per Hour) FAQs
How do you calculate air changes per hour?
Multiply the airflow in CFM by 60 to get cubic feet of air moved per hour, then divide by the room volume in cubic feet: ACH = (CFM × 60) ÷ volume. For example, 168 CFM in a 12 ft × 14 ft × 10 ft room is (168 × 60) ÷ 1,680 = 6 air changes per hour.
How much CFM do I need for a target ACH?
Rearrange the same formula: CFM = (ACH × room volume in cubic feet) ÷ 60. A 250 sq ft room with an 8 ft ceiling is 2,000 cubic feet, so hitting 8 ACH requires (8 × 2,000) ÷ 60 = 266.67 CFM.
What is a good ACH for a room?
It depends on the space. Residential living rooms are typically designed for 6–8 ACH, bedrooms 5–6, and bathrooms 6–7, while offices run 6–8 and classrooms 6–20. Commercial kitchens need 14–60 and repair garages 20–30 for contaminant dilution. ASHRAE 170 requires a minimum of 6 total ACH for a hospital patient room, 12 for an airborne isolation room, and 20 for an operating room.