Water Heater Commissioning Report
Gas-fired storage · 07/29/2026
Outstanding
21
1Equipment & siteThe type you choose decides which measurements the form asks for.Gas-fired storage
Customer & siteNothing set
Company detailsNothing set
2MeasurementsAuto-checkedChecked against the code as you type — including where the code is silent.Nothing recorded
IPC 604.8 requires a pressure reducing valve above 80 psi.
The IPC sets no maximum storage temperature. 120°F is a fixture valve limit; 140°F is a tankless ceiling and the ASHRAE storage recommendation.
Model-specific — record against the rating plate. A 4 in w.c. figure is typical for natural gas, but it is not a target.
Undiluted flue gas at steady state — not air-free. Abort and ventilate if ambient CO exceeds 35 ppm.
3Commissioning checklistOnly what applies to the appliance type you chose.Nothing recorded yet
Relief valve & safety7 checks
The provisions that stop a water heater becoming a pressure vessel.
IPC 504.4 — conforming to ANSI Z21.22. It shall not be used as a means of controlling thermal expansion.
IPC 504.5 — temperature not more than 210°F, pressure not exceeding the tank rating or 150 psi, whichever is less.
IPC 504.4.1 — and there shall be no check valve or shutoff valve between the relief valve and the tank.
Installation3 checks
Clearances, connections and the things that void a warranty.
Do not apply heat to nipples containing a plastic liner — sweating a fitting in place destroys the dielectric and sets up galvanic corrosion.
IRC M1307.3 — not less than 18 in above the floor. Appliances listed as flammable-vapour-ignition-resistant are exempt.
Venting & combustion5 checks
Gas-fired units only.
Category I takes Type B double-wall. Categories II, III and IV take a special vent listed to UL 1738 — commonly PVC, CPVC, polypropylene or AL29-4C stainless on a condensing unit.
NFPA 54 standard method — 50 cubic feet per 1,000 Btu/h of appliance input.
IFGC 501.15 — this is a code requirement, not best practice. The flue must be resized to prevent condensation and supply adequate draft.
Handover6 checks
What the customer was shown and told.