Free HVAC Tune-Up Checklist with Graded Readings

Build and download a free seasonal HVAC tune-up checklist that records the readings and grades them — capacitor µF against the rated µF, amps against nameplate RLA, temperature rise against the rating plate range, and combustion CO on the air-free basis. Cooling, gas heat or heat pump. PDF, Excel, or Word export.

Where should we send it?

Add your email to download this template. It is free, and you only have to do this once.

We use it to send you the occasional template and product update. See our privacy policy.

HVAC tune-up checklist

The seasonal maintenance visit with the numbers on it. Take the readings, enter the unit’s own nameplate figures beside them, and each one is graded against the equipment in front of you — not against a number printed on a form.

Tune-Up Checklist

HVAC · Seasonal Preventive Maintenance

Readings

0

Out of range

0

Checks done

0/14

Findings

0

Cooling tune-up (A/C or heat pump)Nothing recorded yet
1Visit & technicianWho did the tune-up, on what date.
Visit number
Visit date
Technician
License #optional
2Contractor & customerAppears at the top of the finished sheet.
Contractor
Customer / site
3SystemWhat kind of visit this is, and what equipment it was on.
Tune-up type
Equipment identityMake, model, serial
Makeoptional
Modeloptional
Serialoptional
4Measured readingsGradedEnter the nameplate figure beside each reading and it grades itself.

Air side

Total external static pressure
Not measured

Cooling performance

Evaporator temperature split (ΔT)
Not measured

Outdoor unit electrical

Compressor running amps
Not measured
Condenser fan motor amps
Not measured
Run capacitor
Not measured
5Maintenance tasksThe visual and hands-on work behind the readings.
Air side & condensate0 of 6 checked
Filter replaced or cleaned; size and MERV recorded
Blower wheel and housing inspected and cleaned
Evaporator coil inspected and cleaned as needed
Outdoor unit0 of 5 checked
Condenser coil cleaned, fins combed, manufacturer clearances held
Contactor inspected — points, chatter, coil
Refrigerant charge verified by superheat or subcooling at steady state
Controls & closeout0 of 3 checked
Thermostat programming, staging and fan settings confirmed with the customer
Readings and findings reviewed with the customer
Filter size written down and the next visit scheduled
Deficiencies & recommended workoptional

Add to your checklist:

Download your tune-up sheet:

Free · no signup · fully editable

What's included

  • Eight graded readings, six of them judged against this unit's own nameplate rather than a number printed on the form
  • Temperature rise checked against the rise RANGE you type off the rating plate — the one genuinely per-unit heating requirement, and the one most sheets skip
  • Run capacitor graded against the rated µF and the tolerance printed on the can, with ±6% only as an editable default
  • Compressor and condenser fan amps compared to nameplate RLA and FLA
  • Total external static pressure judged against the blower table figure, not against a blanket 0.5 in. w.c.
  • Combustion CO graded on the AIR-FREE basis against the 400 ppm central-furnace threshold, with O₂ correction built in
  • Evaporator ΔT recorded against a target you enter, because target ΔT moves with return humidity and 20°F is not a specification
  • Four visit types — cooling, gas heat, heat pump heat, or a full cooling-plus-heat visit — each showing only the readings and tasks that apply
  • Preventive-maintenance task list covering air side and condensate, outdoor unit, gas heat, heat pump defrost and closeout
  • Every out-of-range reading and every flagged task collected into one findings list at the top of the export
  • Export to PDF, Excel (.xlsx), or Word (.docx)

How to use this template

  1. 1

    Pick the visit type

    Cooling, gas heat, heat pump heat, or the full system. It decides everything else — a cooling visit is never asked for a manifold pressure, and a gas furnace is never asked about its reversing valve.

  2. 2

    Copy the nameplate figures in first

    Rated ESP off the blower table, RLA and FLA off the data plate, rated µF off the capacitor, the rise range and manifold pressure off the rating plate. These are the targets everything else is graded against, and they take thirty seconds at the start of the visit.

  3. 3

    Take the readings

    Each one is graded the moment both numbers are in, and tells you which way it is wrong — a rise above the plate maximum names the limit cycling and the cracked exchanger it leads to, not just "high".

  4. 4

    Work the PM task list

    Filter, blower wheel, coils, condensate and the drain pan safety switch, then the season-specific items. Mark each OK, needs attention or not applicable, and add a note where it matters.

  5. 5

    Download and leave it with them

    PDF, Excel or Word. Everything out of range appears in one list at the top with the reason, so the customer sees a measured number rather than a tick box.

Why a tune-up sheet with no numbers on it proves nothing

Most tune-up checklists in circulation are tick boxes. Filter — checked. Coil — checked. Electrical — checked. A furnace can pass every line of that sheet while it is over-firing by half an inch of water column, running a 95°F rise against a rating plate that stops at 70, and putting 450 ppm of carbon monoxide up the flue. Nothing on a box-ticking form catches any of it, and nothing on it gives the customer a reason to believe the visit happened at all.

This builder records the readings and grades them, and it grades most of them against the unit in front of you rather than a number we printed. Temperature rise is the clearest example. Every gas furnace rating plate states its own rise range — 30 to 60, 45 to 75, 50 to 80 — and the measured rise has to land inside that specific range. Below the minimum the blower is moving too much air and the heat exchanger can condense and corrode; at or above the maximum the furnace cycles on the high limit and the exchanger cooks, which is how they crack. There is no universal range to print, so the form makes you type the plate range in and then does the comparison.

The same discipline applies everywhere a number would be tempting. Capacitors are graded against the rated µF and the tolerance printed on the can — ±6% is what most OEM-grade HVAC run capacitors are marked to, but ±5% and ±10% parts are sold, so the tolerance is an editable field rather than a constant. Manifold pressure is compared to the rating plate, because 3.5 inches water column is a common natural-gas setting and not a specification; LP units sit near 10 to 11, and two-stage valves differ per stage. Static pressure is judged against the blower table figure, because grading every unit at 0.5 in. w.c. fails correctly installed high-static equipment. And evaporator ΔT is recorded against a target you enter, because target split moves with the humidity of the return air: the 18 to 22°F everyone quotes only holds near 45 to 55% relative humidity, and a correctly operating system on an 80°F dry-bulb, 71°F wet-bulb return legitimately reads about 15°F.

Carbon monoxide gets the most careful handling on the sheet, because it is the reading that can stop a job and the one most often quoted on the wrong basis. The 400 ppm threshold for a central furnace is AIR FREE — that is how the ANSI/BPI-1200 thresholds table, the National Fuel Gas Code and the ANSI Z21.47 appliance listing all state it. It is routinely confused with the BPI Building Analyst 26 / 100 / 400 ppm action levels, which are undiluted flue gas and are a different measurement from a different document. This form says which basis it is applying, converts your as-measured reading using the flue O₂ when you enter it, and flags anything above 100 ppm air free as worth chasing even though it is technically inside the standard.

Related templates

More free downloads for your HVAC template library.

Tune-Up Checklist FAQs

What temperature rise is acceptable on a gas furnace?

Whatever the rating plate on that furnace says, and nothing else. The plate states a range — commonly something like 30–60°F, 45–75°F or 50–80°F — and the measured rise has to fall inside it. There is no industry-wide range to quote, which is why this form asks you to type the plate figures in rather than printing numbers of its own. Aim near the middle of the range for best performance. Below the minimum, the blower is moving too much air: the supply feels cool to the customer and the heat exchanger can condense and corrode. At or above the maximum, the furnace limit-cycles and the exchanger overheats, which is the failure mode that ends in a crack. Measure the return at the furnace and the supply several feet downstream, so the probe has no line of sight to the heat exchanger and is not reading radiant heat.

Almost certainly yes, and this is the argument worth settling with the label rather than with opinion. Most OEM-grade HVAC run capacitors are marked ±6%, which puts a 45 µF part's acceptable band at 42.3 to 47.7 µF — a reading 5% down at 42.75 µF is inside tolerance and is a pass, not a sale. But ±6% is not universal: ±5% and ±10% parts are both sold, and the tolerance is printed on the can. That is why this builder takes the tolerance as an editable field defaulted to 6 rather than hard-coding it. What a low-but-in-tolerance reading does justify is watching the motor's amp draw, because a weakening capacitor shows up there first.

Above 400 ppm air free in the flue on a central furnace. That is the threshold in the ANSI/BPI-1200 CO thresholds table and it matches the National Fuel Gas Code figure and the ANSI Z21.47 appliance listing limit. Over it, the appliance should not be left in service — shut it down, tag it, and correct the cause. The number people get wrong is the basis: 400 ppm air free is not the same as 400 ppm as measured, and it is not the same as the BPI Building Analyst 26 / 100 / 400 ppm action levels, which are undiluted flue gas from a different document. Air-free CO = measured CO × 20.9 ÷ (20.9 − flue O₂%), so a reading of 87 ppm at 5% O₂ is really 114 ppm air free. Most analyzers show air-free CO directly; this form converts for you if you enter the O₂. Separately, well below the threshold, anything over about 100 ppm air free is worth chasing — that is the level most manufacturers and trainers actually work to.

It depends on the air entering the coil, not on how many years the person answering has been in the trade. The 18 to 22°F rule of thumb only holds around 45 to 55% relative humidity. As the return gets more humid the coil spends more of its capacity condensing moisture and less of it dropping temperature, so the dry-bulb split narrows even though total capacity is normal — a correctly operating system on an 80°F dry-bulb, 71°F wet-bulb return reads about 15°F. Take the target from the manufacturer's chart or from a target-ΔT table using the measured return dry-bulb and wet-bulb, enter it here, and the reading is graded against that. Leave it blank and the split is recorded without a verdict, which is the honest outcome rather than a made-up pass.

The figure on the appliance rating plate. Natural gas furnaces commonly sit near 3.5 inches water column and LP near 10 to 11, but those are common settings, not specifications — two-stage valves have a different figure per stage, and the plate is the authority. Gas control manufacturers publish an adjustment latitude of about ±0.3 in. w.c. from the factory-set rate, so this form treats a reading further off the plate than that as needing a reset. It matters in both directions: over-firing is a leading cause of cracked heat exchangers, and under-firing starves the appliance and drives CO up.

A maintenance checklist records what was done. This records what was measured, and grades it. The two are complementary — this builder still carries the preventive-maintenance task list for the air side, the outdoor unit, gas heat, heat pump defrost and closeout — but the readings are the point. When a customer asks what they paid for, "temperature rise 88°F against a plate range of 45 to 75, limit cycling, blower speed corrected" is an answer. "Heating — checked" is not.

Four things this form makes explicit. Force a defrost rather than trusting the board, and watch it initiate, shift the reversing valve cleanly, terminate on the sensor or timer as configured, and actually drain the melt. Check the reversing valve and solenoid in both modes — a valve that shifts fine in July can hang in a February defrost. Verify auxiliary and emergency heat staging and lockouts against the thermostat configuration, because a mis-set outdoor lockout leaves resistance heat running alongside a perfectly good heat pump all winter with nothing on the equipment to tell the customer. And confirm the outdoor unit is elevated clear of the snow and ice line with an open base pan drain, or it re-freezes its own defrost melt.

Because a switch that has never been tested is a switch that does not work, and this is the one that turns a plugged condensate drain into a ceiling claim. IMC 307.2.3 requires a water-level detection device conforming to UL 508 that shuts off the equipment served — installed in the primary drain line, the overflow line, or in the equipment drain pan above the primary connection and below the pan's overflow rim. Lift the float and confirm the equipment actually stops. Confirming the device is present is not the same check.

No. It is the technician's record of a maintenance visit. Code and standard citations appear to explain why something is checked and where a threshold comes from — they do not certify the installation, and approval rests with the authority having jurisdiction. Manufacturer instructions govern wherever they are more specific than anything printed here.

Your tune-up sheet carries real numbers. Larry answers the phone while you take them.

We will run your numbers on the call and tell you if the maths does not work for a shop your size. That happens, and it is a cheaper conversation than finding out three months in.

Get a demo