Installation Checklist
HVAC · New system installation · 09/11/2026
1Project & systemThe system type and fuel decide which phases this install actually has.Nothing set
SystemAn all-electric install has no gas and venting phase; a ductless mini-split has no duct phase. Neither is greyed out — it simply is not there, and it does not count against your sign-off total.Split system A/C · Electric only
JurisdictionValues on this checklist are from the 2021 IMC, the 2021 IRC (mechanical and fuel gas), the 2021 IECC and the 2023 NEC. Adoption and edition are local decisions and amendments are common — confirm with your authority having jurisdiction.Not set — editions and amendments vary
Site addressNothing set
Company detailsNothing set
2PhasesGatedRough-in through final. A phase unlocks when the one before it is signed.Nothing recorded yet
Rough-inIn progress
Before anything is covered. Load calculation on file, equipment location proved for clearance and service access, penetrations and routes set.
Equipment setLocked
The unit in its final position, installed to its listing and the manufacturer’s instructions, with the clearances measured rather than assumed.
Refrigerant line setLocked
Sized, brazed under nitrogen, pressure tested with an inert gas, evacuated and proved by a standing decay test, insulated and supported.
No target entered — read it off the nameplate, or this reading is recorded rather than judged.
No target entered — read it off the installation instructions, or this reading is recorded rather than judged.
CondensateLocked
Primary drain, trap and slope, plus the auxiliary protection IMC 307.2.3 requires wherever an overflow could damage the building.
Judged against 1 % fall.
ElectricalLocked
Disconnect within sight with its working space clear, overcurrent protection and conductors sized to the nameplate, bonding and controls landed.
No target entered — read it off the nameplate, or this reading is recorded rather than judged.
DuctLocked
Sealed, supported, insulated for its location and leakage tested where the energy code requires it. Return path provided and legal.
Judged against 4 cfm25 / 100 sq ft.
FinalLocked
Everything outstanding cleared, labelling and filter in place, AHJ final passed, and the system handed to start-up and commissioning.
Airflow, refrigerant charge, total external static pressure, temperature split and combustion readings are start-up measurements. They belong on the equipment start-up report and are deliberately not repeated here.