Free HVAC Installation Checklist Template

Build and download a free phase-gated HVAC installation checklist — rough-in, equipment set, line set, condensate, gas and venting, electrical, duct, final. Each phase is signed before the next opens, each item carries the IMC, IRC, IECC or NEC section behind it, and the evacuation reading is judged against your installation instructions rather than against a number we invented. PDF, Excel, or Word export.

Where should we send it?

Add your email to download this template. It is free, and you only have to do this once.

We use it to send you the occasional template and product update. See our privacy policy.

Build your installation checklist

Eight phases in order, each one locked until the phase before it is signed. Rough-in is behind drywall by the time the duct is insulated, so the sequence is the record.

Installation Checklist

HVAC · New system installation · 09/11/2026

1Project & systemThe system type and fuel decide which phases this install actually has.
Title
Start date
Projectoptional
Project #optional
General contractoroptional
Permit #optional
SystemSplit system A/C · Electric only
System type
Fuel
Outdoor unitoptional
Indoor unitoptional
Line set length (ft)optional
JurisdictionNot set — editions and amendments vary
Authority having jurisdiction
Code edition
Site addressNothing set
Company detailsNothing set
2PhasesGatedRough-in through final. A phase unlocks when the one before it is signed.
Rough-inIn progress

Before anything is covered. Load calculation on file, equipment location proved for clearance and service access, penetrations and routes set.

Manual J load calculation and Manual S selection on file before rough-inGates sign-off
Equipment location proved for listed clearance to combustibles and service accessGates sign-off
Attic or underfloor access route sized before the ceiling closes
Phase sign-off
Signed byoptional
Dateoptional
Inspection / record #optional
Equipment setLocked

The unit in its final position, installed to its listing and the manufacturer’s instructions, with the clearances measured rather than assumed.

Installed per its listing and the manufacturer’s installation instructions; instructions left on siteGates sign-off
Clearance to combustibles measured at or above the label valueGates sign-off
30 in by 30 in level working space still clear at the control side after the unit is setGates sign-off
Phase sign-off
Signed byoptional
Dateoptional
Inspection / record #optional
Refrigerant line setLocked

Sized, brazed under nitrogen, pressure tested with an inert gas, evacuated and proved by a standing decay test, insulated and supported.

Line sizes, total length and vertical lift inside the manufacturer’s tablesGates sign-offPer manual
Brazed joints made under a flowing dry-nitrogen purgeGates sign-off
Vapour (suction) line insulated to R-3 with a vapour-tight jacketGates sign-off
Tests & measurements
Nitrogen pressure test

No target entered — read it off the nameplate, or this reading is recorded rather than judged.

Actual (psig)
Held (min)
Dateoptional
Target
Evacuation — standing vacuum decay

No target entered — read it off the installation instructions, or this reading is recorded rather than judged.

Actual (microns)
Held (min)optional
Dateoptional
Target
Phase sign-off
Signed byoptional
Dateoptional
Inspection / record #optional
CondensateLocked

Primary drain, trap and slope, plus the auxiliary protection IMC 307.2.3 requires wherever an overflow could damage the building.

Primary drain not less than 3/4 in and never decreasing toward the point of disposalGates sign-off
Drain trapped as the equipment manufacturer requires, with the depth set for the blowerGates sign-off
Auxiliary overflow protection provided where an overflow could damage the buildingGates sign-off
Tests & measurements
Condensate drain slope

Judged against 1 % fall.

Actual (% fall)
Held (min)optional
Dateoptional
Targetoptional
Phase sign-off
Signed byoptional
Dateoptional
Inspection / record #optional
ElectricalLocked

Disconnect within sight with its working space clear, overcurrent protection and conductors sized to the nameplate, bonding and controls landed.

Disconnecting means within sight from and readily accessible from the equipmentGates sign-off
Working space at the disconnect meets NEC 110.26(A)Gates sign-off
Branch-circuit conductors sized at or above the nameplate minimum circuit ampacityGates sign-off
Tests & measurements
Branch-circuit overcurrent device vs nameplate MOCP

No target entered — read it off the nameplate, or this reading is recorded rather than judged.

Actual (A)
Held (min)optional
Dateoptional
Target
Phase sign-off
Signed byoptional
Dateoptional
Inspection / record #optional
DuctLocked

Sealed, supported, insulated for its location and leakage tested where the energy code requires it. Return path provided and legal.

Joints, seams and connections fastened and sealedGates sign-off
Ducts supported at the required spacing without sag or compression
Duct insulation R-value correct for the location and the duct diameterGates sign-off
Tests & measurements
Duct leakage test

Judged against 4 cfm25 / 100 sq ft.

Actual (cfm25 / 100 sq ft)
Held (min)optional
Dateoptional
Targetoptional
Phase sign-off
Signed byoptional
Dateoptional
Inspection / record #optional
FinalLocked

Everything outstanding cleared, labelling and filter in place, AHJ final passed, and the system handed to start-up and commissioning.

Every open or failed item from the earlier phases clearedGates sign-off
Equipment, disconnect and shutoffs labelled; nameplates legible and not obscured
Filter installed, rack sealed, and the size written down for the owner
Phase sign-off
Signed byoptional
Dateoptional
Inspection / record #optional

Airflow, refrigerant charge, total external static pressure, temperature split and combustion readings are start-up measurements. They belong on the equipment start-up report and are deliberately not repeated here.

Add to your checklist:

Download your checklist:

Free · no signup · fully editable

What's included

  • Eight phases worked in order — rough-in, equipment set, refrigerant line set, condensate, gas and venting, electrical, duct, final — with each one locked until the phase before it is signed
  • Out-of-order sign-offs recorded and printed as such, because on a new install the order is the evidence
  • Every item carrying its section: IMC 306 and 307, IRC M1305, M1306, M1411, M1601 and M1602, IRC fuel gas G2407, G2417, G2419 and G2427, 2021 IECC R403.3 and R403.4, NEC 440.14, 440.4(B) and 110.26
  • Six recorded tests — nitrogen pressure test, evacuation decay, condensate slope, gas piping test, overcurrent device against nameplate MOCP, and duct leakage
  • Evacuation and nitrogen pressure judged against the figure you read off the installation instructions and the nameplate, never against a hard-coded number, because neither has one in code
  • Readings taken with no acceptance figure behind them reported as "recorded", not as "passed", and collected into their own list
  • The gas and venting phase dropping out entirely on an all-electric install, and the duct phase on a ductless mini-split
  • Failed and pending items collected into an open-items list at the top of every export
  • A final phase that hands the system to start-up and commissioning instead of repeating it
  • Export to PDF, Excel (.xlsx), or Word (.docx)

How to use this template

  1. 1

    Set the system type and fuel first

    They decide which phases exist. An all-electric heat pump never sees the gas and venting phase; a ductless mini-split never sees the duct phase. Nothing is greyed out — it simply is not there, and it does not count against your sign-off total.

  2. 2

    Work rough-in before anything is covered

    Load calculation on file, equipment location proved with a tape for both the listed clearance to combustibles and the 30 by 30 working space, attic route sized, penetrations and firestopping set. This is the only phase where the condensate fall can still be fixed.

  3. 3

    Sign each phase before opening the next

    A phase turns green and offers its sign-off once every critical item is complete or N/A and no test has failed. Signing anyway is allowed — crews do work out of order — but the export says so, in the open items list.

  4. 4

    Record the tests against the right figure

    Condensate slope, gas test pressure and duct leakage are graded against the code values. Nitrogen test pressure comes off the nameplate and the evacuation target comes out of the installation manual, so you type those in. Leave them blank and the reading prints as recorded, not as a pass.

  5. 5

    Close the final phase and hand off to start-up

    Clear the open items, get the AHJ final, then move to the equipment start-up report for airflow, charge, static pressure and combustion. Those are commissioning readings and this sheet deliberately does not collect them twice.

  6. 6

    Download and file it

    Export to PDF, Excel or Word. Anything failed or pending sits at the top, and every phase prints its sign-off, its state, and the code section behind each check.

Why an installation checklist is phase-gated, and what it refuses to print

A new HVAC installation is not one job, it is eight, and seven of them get buried by the eighth. The condensate fall stops being fixable the moment the ceiling closes. The listed clearance to combustibles stops being measurable the moment the furnace is set and the closet is trimmed. The line-set evacuation stops being provable the moment the charge goes in. That is why this checklist gates: rough-in, equipment set, refrigerant line set, condensate, gas and venting, electrical, duct, final, each one locked until the one before it is signed. Most free installation checklists in circulation are a flat list of forty tick boxes with no order and no consequence, which is a to-do list, not a record. This one records who signed what, when, and whether it was signed in sequence — and if it was not, it prints that too, because on a new build the order is most of the evidence.

The items are cited rather than asserted. Condensate is the section people get wrong most often, so it is worth stating precisely: IMC 307.2.2 requires the primary drain to be not less than 3/4 inch internal diameter and to never decrease toward the point of disposal; IMC 307.2.1 requires a fall of not less than 1/8 unit vertical in 12 units horizontal, which is exactly 1 percent, stated two ways; IMC 307.2.4 requires the drain to be trapped as the equipment manufacturer requires and prints no trap depth at all, because depth depends on the blower static and on which side of the blower the drain sits. IMC 307.2.3 then gives four alternatives for auxiliary protection wherever an overflow could damage the building — an auxiliary pan not less than 1-1/2 inches deep and 3 inches larger than the unit with its own drain, a separate overflow line from the equipment pan to a conspicuous point, an auxiliary pan with a UL 508 water-level detection device, or a UL 508 device in the primary drain or the equipment pan. It is one of the four, not all four, and IMC 307.2.3.1 adds the case everybody forgets: a down-flow coil with nowhere to put a pan gets a monitoring device inside the primary pan instead.

The duct numbers move by code edition, so this checklist names its edition. Under the 2021 IECC, R403.3.1 requires supply and return ducts in attics to be insulated to R-8 at 3 inches diameter and larger and R-6 below that, with R-6 and R-4.2 in other portions of the building, and R403.3.6 caps total leakage at 4.0 cfm per 100 square feet of conditioned floor area for a post-construction test or a rough-in test with the air handler installed, dropping to 3.0 cfm where the air handler is not yet in. The 2018 edition and a long list of state amendments read differently, which is why the target is editable and why the sheet asks which edition your permit was pulled under rather than assuming. Duct sealing is IRC M1601.4.1 — mastic, mastic-plus-embedded-fabric, gaskets, welds, liquid sealants or tapes marked 181B-FX or 181B-M, which specifically excludes the cloth-backed rubber-adhesive tape still sold as duct tape. Support is M1601.4.4 at 10 feet or the manufacturer's spacing; the "every 4 feet" figure quoted for flex comes from the ADC flexible-duct standard and the duct maker's literature, not from the IRC, and this sheet says so rather than citing the IRC for a number the IRC does not contain.

Two numbers are deliberately not hard-coded, and that is the most important design decision in the whole builder. The first is the evacuation target. "Pull to 500 microns" is an industry convention, not a code requirement, and it is not even a universal manufacturer figure — several manufacturers publish 300 microns or lower as the condition of the compressor warranty. Worse, hitting any number once proves nothing: a system that climbs and levels off is wet, a system that climbs without levelling is leaking, and only the standing decay test tells them apart. So the evacuation row has no built-in pass threshold. It offers 500 as a placeholder, asks you for the figure from the installation instructions for that unit, and if you leave it blank it reports your reading as recorded rather than as passed. The second is the nitrogen pressure test: IMC 1110.5 requires the system to be held for not less than 60 minutes at not less than the lower of the design pressures or the relief-device setting, and points at the nameplate for the number. There is no national psi figure to print, so the sheet asks for the one on the plate. The same discipline applies to outdoor unit clearance, where no code figure exists at all and the familiar 24-inch and 60-inch values are manufacturer numbers that vary by model, and to direct-vent terminal clearances, where IRC G2427.8 tiers by appliance input in Table G2427.8 — so the mechanical-draft clearances the code states in prose are printed, and the direct-vent tiers are not, because a wrong tier is a carbon monoxide problem rather than a paperwork one.

Related templates

More free downloads for your HVAC template library.

Installation Checklist FAQs

How is this different from your change out checklist?

A change-out is a replacement, and its risks are the old system: recovering the existing charge under EPA Section 608 before anything is opened, deciding whether the existing line set can be reused, and finding out that the duct system that was already over its rated static is still over it. This is a new installation, so there is nothing to recover and nothing to reuse — the risks are workmanship that gets concealed. Rough-in happens before drywall, the condensate fall has to be built rather than inherited, and every phase is gated because the evidence disappears. If you are replacing equipment in an existing house, use the change out checklist. If you are installing into new construction or a full new system, use this one.

Because those are commissioning readings, not installation workmanship, and they belong on the equipment start-up report. Total external static pressure, measured airflow against the rated CFM, superheat or subcooling at steady state, temperature split and combustion analysis are all taken after the system runs — which by definition is after this checklist is finished. The final phase hands the system over to start-up rather than duplicating it, so you get one authoritative record of each thing rather than two that can disagree.

Whatever the installation instructions for that unit say. 500 microns is the common industry figure and it is a reasonable default, but it is not in any code and manufacturers vary — several require 300 microns or lower as a warranty condition. More importantly, the number on its own is not the test. Isolate the pump and watch the gauge: a system that rises and levels off has moisture in it, a system that rises without levelling has a leak, and a system that holds is dry and tight. That is why the builder records the reading and the decay hold, and why it will report a reading as recorded rather than passed if you have not told it what the manual asked for.

Not less than 3/4 inch internal diameter, never decreasing toward the point of disposal (IMC 307.2.2), a fall of not less than 1/8 inch per foot — 1 percent — on horizontal runs (IMC 307.2.1), trapped as the equipment manufacturer requires (IMC 307.2.4, which states no depth of its own), terminated at an approved point that does not create a nuisance (IMC 307.2.1), and auxiliary overflow protection by one of four methods wherever an overflow could damage building components (IMC 307.2.3, mirrored at IRC M1411.3.1). Down-flow coils and anything else with no place for a secondary pan get a water-level monitoring device inside the primary pan under IMC 307.2.3.1. Larger equipment sizes up from Table 307.2.2 — 1 inch to 40 tons, 1-1/4 inch to 90 tons, and so on.

Within sight from and readily accessible from the equipment, under NEC 440.14. "Within sight" is defined in Article 100 as visible and not more than 50 feet distant, so the practical answer is that you must be able to see it from the unit. It may not be mounted on a panel that has to be removed to service the equipment, and it may not obscure the nameplate. Since the 2023 NEC, 440.14 also calls out the 110.26(A) working space explicitly — and the usual violation is a line set or a run of liquidtight cutting diagonally through that space, installed by us rather than by the electrician.

Under the 2021 IECC it is 4.0 cfm per 100 square feet of conditioned floor area for a post-construction test, or for a rough-in test with the air handler installed, and 3.0 cfm where the air handler is not yet in at the time of the test. Systems serving 1,200 square feet or less get a 50 cfm allowance instead. Testing is to ANSI/RESNET/ICC 380 or ASTM E1554 at 0.1 inch water gauge. But those are the 2021 model figures — the 2018 edition reads differently and several states amend both, so the target on the form is editable and the export prints which edition you cited.

Yes, and the sheet records that you did. Real jobs run out of sequence — the electrician is on site a week early, the gas meter is late, the duct crew comes back after the drywallers. Refusing to record what happened would only get the form abandoned. So a phase whose predecessors are unsigned shows as locked, signing it anyway is permitted, and the export prints "signed off while an earlier phase was still open" in the open items list, with the note that the work it covers may already be concealed. That is a materially different document from one that quietly lets everything be ticked at the end of the job.

No. It is the installing contractor's record of the work performed and the tests taken, and every export says so. Code citations appear to explain why something was checked, not to certify the installation — the authority having jurisdiction inspects and releases the work. The values on the sheet are from the 2021 IMC, the 2021 IRC mechanical and fuel gas provisions, the 2021 IECC and the 2023 NEC; adoption, edition and local amendment are all decisions your AHJ makes, and the form asks who that is.

Your checklist proves the install. Larry answers the phone while you finish it.

We will run your numbers on the call and tell you if the maths does not work for a shop your size. That happens, and it is a cheaper conversation than finding out three months in.

Get a demo