Free HVAC Diagnostic Checklist Template

Build and download a free HVAC diagnostic checklist. Pick the complaint, enter the readings, and the form computes target superheat from the charging chart inputs, grades subcooling against the nameplate, and reads the two together to tell you whether you are looking at an undercharge, an overcharge, a restriction or a compressor that has stopped pumping. PDF, Excel, or Word export.

Where should we send it?

Add your email to download this template. It is free, and you only have to do this once.

We use it to send you the occasional template and product update. See our privacy policy.

Build your diagnostic report

Pick the complaint and the metering device, then record what you measured. The form computes the target where one honestly exists — and tells you where one does not.

HVAC Diagnostic Checklist

Not cooling enough · 09/11/2026

Outstanding

27

1Complaint & systemThe complaint shapes the checks; the metering device decides which reading carries the charge.
Customer complaint

Take total external static pressure BEFORE adjusting charge. Low airflow drives superheat down and subcooling up on a fixed orifice, which reads as an overcharge — recovering refrigerant off a dirty blower wheel makes the system worse.

System type
Metering device
Refrigerant
Service date
Make
Model
Serial #
Full charge (lb)optional
Customer & siteNothing set
Company detailsNothing set
2Air sideAuto-checkedTaken first, because low airflow imitates a charge fault on the gauges.
Return dry bulb (°F)optional
Return wet bulb (°F)optional
Supply dry bulb (°F)optional
Static pressure
Total external static (in. w.c.)optional
Rated external static (in. w.c.)optional
3Refrigerant circuitAuto-checkedThe target is computed where one honestly exists, and asked for where it is nameplate data.
Superheat measured (°F)optional
Subcooling measured (°F)optional
Nameplate subcooling target (°F)optional
4ElectricalAuto-checkedMeasured against the ratings on the components, not against rules of thumb.
Run capacitor rated (µF)optional
Run capacitor measured (µF)optional
Compressor amps (A)optional
Compressor RLA (A)optional
Condenser fan amps (A)optional
Condenser fan FLA (A)optional
5Fault isolation checklistScoped to the complaint and the system you chose.
Arrival & conditions6 checks

What was true before anything was touched.

Complaint reproduced and verified on site
Thermostat mode, setpoint and configuration checked
Line voltage, disconnect and breaker confirmed
Air side7 checks

Checked before the charge, because low airflow imitates a charge fault.

Blower wheel clean and secure on the shaft
Evaporator coil face inspected for loading
Condenser coil clean and unobstructed
Refrigerant circuit5 checks

The circuit itself, alongside the readings above.

Leak search performed where the readings indicate a loss of charge
Refrigerant recovered to a certified machine before opening the circuit
Suction line insulation intact along its full length
Electrical & controls4 checks

The parts that stop a healthy refrigerant circuit from running.

Run capacitor measured under load and compared to its rating
Contactor pulling in with clean, unwelded contacts
Supply voltage checked under load, not at rest
Findings & disposition5 checks

What was concluded and what happens next.

Root cause identified and supported by the readings above
Repair completed, or quoted and declined
Readings re-taken after the repair to confirm the fix
6Root causeTie the conclusion to the readings above — a cause nothing supports is a guess.
Probable causes — Not cooling enough6 listed
  • Restricted airflow — filter, blower wheel, evaporator coil face, closed or undersized ductwork
  • Undercharge from a slow leak — superheat high, subcooling low
  • Dirty condenser coil — high head pressure, high subcooling, poor capacity
  • Liquid line restriction — drier or metering device: high superheat AND high subcooling together
  • Compressor no longer pumping to capacity — superheat and subcooling both low
  • Equipment undersized, duct losses, or the load has changed (added room, failed insulation)

Add to your report:

Download your report:

Free · no signup · fully editable

What's included

  • Seven complaints — no cooling, not cooling enough, no heat, short cycling, ice on the coil, high bill and noise — each with its own probable-cause list and the one step that most often gets skipped on that call
  • Target superheat computed from indoor wet bulb and outdoor dry bulb, the way the fixed-orifice charging chart does it, with the reading graded against it as you type
  • Superheat left ungraded on a TXV or EEV, because the valve sets superheat and grading it there reports a working valve as a charge fault
  • Subcooling graded against the nameplate figure you enter — never against an invented universal target
  • The superheat and subcooling pattern read together: high superheat with low subcooling is an undercharge, high with high is a restriction, low with low is a compressor that has stopped pumping
  • Total external static pressure judged against the equipment’s own rated ESP, not against a hard-coded 0.5 in. w.c.
  • Run capacitor measured against the rating on the can at its marked tolerance, and amp draw against nameplate RLA and FLA
  • The evaporator split computed and reported with its wet-bulb caveat, and deliberately never graded pass or fail
  • EPA obligations stated correctly for 2026 — the venting prohibition at any charge size, and the leak repair threshold routed by which refrigerant is actually in the machine: 50 lb under 40 CFR 82.157 for ozone-depleting refrigerants, 15 lb under 40 CFR 84.106 for HFCs
  • Faults collected into a list at the top of the export, with a root-cause box underneath
  • Export to PDF, Excel (.xlsx), or Word (.docx)

How to use this template

  1. 1

    Pick the complaint

    It shapes the whole form. An ice complaint gets the thaw-first instruction, a no-heat call on a heat pump gets the reversing valve and defrost checks, a noise call gets bearings and balance. Each complaint also carries its own probable-cause list onto the export.

  2. 2

    Set the metering device before you record anything

    This is the choice everything else hangs on. A fixed orifice cannot regulate superheat, so superheat is the charge. A TXV or EEV holds superheat at its own setting, so on those systems superheat describes the valve and subcooling carries the charge.

  3. 3

    Take the air side first

    Static pressure, return wet bulb, return and supply dry bulb. Low airflow drives superheat down and subcooling up, which reads exactly like an overcharge — recovering refrigerant off a loaded blower wheel leaves the system worse than you found it.

  4. 4

    Then the refrigerant circuit

    Indoor wet bulb and outdoor dry bulb give you the target superheat. Enter the nameplate subcooling figure and your measured subcooling. The form reads the pair and names the probable cause.

  5. 5

    Work the checklist and state the root cause

    Mark each check OK, Fault or N/A. Anything marked Fault is collected at the top of the export, and the root-cause box underneath is where you tie it to the readings — a cause no reading supports is a guess, and the form is built to make that obvious.

  6. 6

    Download and leave it with them

    Export to PDF, Excel or Word. The probable cause banner sits at the top, faults come next, and the readings follow with what each one means.

The 20-degree split, and the three questions techs actually argue about

Most diagnostic checklists in circulation are a grid of boxes. They record that you looked at something without helping you decide what it meant. This one is built the other way round: every reading it asks for is graded against something — a computed target, a nameplate figure, or a rating on the equipment — and the ones that cannot honestly be graded are recorded and explained instead of quietly given a number that does not exist.

That last part is the whole difference, and the evaporator split is the clearest example. "You want a 20-degree delta T" is the most repeated line in residential HVAC and it is wrong often enough to be dangerous. The dry-bulb split across an evaporator depends on the moisture in the entering air, not just its temperature. On humid return air the coil spends its capacity condensing water instead of dropping temperature, so a perfectly healthy system reads a narrower split — and a tech chasing 20 degrees will add refrigerant to a system that did not need it. Work it on a psychrometric chart and there is no single target to publish. So this form computes the split, tells you what the wet bulb implies about it, and never issues a pass or a fail on it. Airflow gets its verdict from total external static pressure against the equipment’s own rated ESP, which is a real number printed on a real data tag.

The second argument is superheat or subcooling, and the answer is that it depends entirely on the metering device. A fixed orifice — a piston or a cap tube — has no way to regulate anything, so the superheat leaving the evaporator is a direct readout of how much refrigerant is in the system. That is why the charging chart exists, and why it wants indoor wet bulb and outdoor dry bulb: the target moves with the load. A correct charge reads high superheat on a mild day and low on a hot one, on purpose. A TXV or EEV is a different machine. It actively modulates to hold superheat at its own setting, so on a TXV system superheat tells you whether the valve is working, not whether the charge is right — subcooling against the manufacturer’s figure is the charge indicator there. This form switches its grading when you switch the metering device, and it will not grade superheat on a TXV at all, because a working valve holding 12 degrees would otherwise be reported as a fault.

The third is what a high static pressure actually means, and the answer is simple enough that it is worth stating plainly: the blower cannot move its rated airflow. Nothing more specific than that, until you split the reading. A high number on the return side points at the filter, the return grille or the return duct; a high number on the supply side points at the coil or the supply trunk. What it is not is a licence to start adjusting charge — and the form says so, because low airflow and an overcharge produce the same pair of readings and only one of them is fixed by recovering refrigerant. The same discipline runs through the electrical section: RLA is a listing-derived ceiling back-calculated from the maximum current the compressor’s overload will tolerate, not a figure the compressor is supposed to reach, so a unit drawing 60 percent of its RLA is healthy and this form will not tell you otherwise.

Related templates

More free downloads for your HVAC template library.

Diagnostic Checklist FAQs

Is a 20-degree delta T actually a real target?

No. It is a rule of thumb that ignores the single biggest variable. The dry-bulb split across an evaporator depends on the water vapour content of the air entering it: on a humid return the coil spends much of its capacity on latent removal — condensing moisture — and drops the temperature less, so a healthy system reads a narrower split. On a dry return the same system reads wider. Work the two cases on a psychrometric chart and you get different answers from identical equipment, which is why no manufacturer publishes a single number. This form computes your split, tells you what your return wet bulb implies about it, and refuses to pass or fail it. If you want an airflow verdict, take static pressure against the equipment’s rated ESP — that one is a real comparison against a real number.

Whichever one the metering device is not controlling. A fixed orifice (piston or cap tube) cannot regulate anything, so superheat at the compressor inlet is a direct readout of charge, and the target comes off the charging chart against indoor wet bulb and outdoor dry bulb. A TXV or EEV actively modulates to hold superheat at its own setting, so on those systems superheat describes the valve and subcooling against the manufacturer’s figure describes the charge. Getting this backwards is how a working TXV holding a normal superheat gets diagnosed as an undercharge. This builder asks for the metering device first and grades accordingly.

Whatever the nameplate or the charging chart for that unit says. You will see 8 to 12 degrees quoted everywhere and it is a fair description of what a lot of residential equipment specifies — but it is manufacturer data, not a standard, and units specifying well outside that range exist. This form asks for the figure off the unit and grades your reading against that. Enter nothing and it records your subcooling and says plainly that it has nothing to judge it against, rather than inventing a target and failing a correctly charged system.

That the blower cannot move its rated airflow against the resistance in front of it — and on its own, nothing more specific. The useful move is to split the reading. High on the return side means the filter, the return grille or the return ductwork; high on the supply side means the coil or the supply trunk. Compare it to the equipment’s rated external static, not to a rule of thumb: 0.5 inches water column is typical of PSC equipment and ACCA Manual D designs to the rated figure, but ECM equipment is commonly rated higher, so a unit rated 0.8 running at 0.7 is fine and a form that fails it at 0.5 is wrong.

Possibly, but restricted evaporator airflow produces exactly the same pair of readings, and recovering refrigerant off an airflow problem leaves you worse than you started. That is why this form asks for static pressure and flags the pattern with a caveat when the air side is high or has not been measured at all. Check the filter, blower wheel and the entering face of the evaporator coil before you touch the charge. The four patterns worth memorising: high superheat with low subcooling is an undercharge, low with high is an overcharge or low airflow, high with high is a restriction between the condenser and the evaporator, and low with low is a compressor that has stopped pumping.

No, and this is one of the most common misreadings in the trade. RLA stands for Rated Load Amps, but it is not the current the compressor is expected to draw — it is a listing figure, back-calculated from the maximum continuous current the internal overload will tolerate, divided by roughly 1.44 to 1.56 depending on the manufacturer. A healthy compressor normally runs well below it. This form flags an over-RLA reading, because that means the overload is heading for a trip, and it never treats a low reading as a fault.

It depends on the refrigerant, and this is where most templates go wrong — they print one universal number. There are two rules and they run in parallel. An ozone-depleting refrigerant such as R-22 falls under 40 CFR 82.157, which still exists and still uses a 50-pound full charge; EPA's 2020 rule rescinded only the 2016 extension of those provisions to non-ODS substitutes, not the section itself. An HFC or regulated substitute falls under 40 CFR 84.106, created by the AIM Act Emissions Reduction and Reclamation rule, at 15 pounds or more with compliance from 1 January 2026. EPA describes part 84 subpart C as applying more broadly, to refrigerants that were not regulated under part 82 and to appliances with smaller charges — broader coverage alongside the older rule, not a replacement of it. The practical consequence: a 20-pound R-22 machine is under neither rule, because 84.106 does not reach R-22 and 82.157 needs 50 pounds. Telling that customer they have a leak repair obligation invents one. Above whichever threshold applies, a comfort cooling appliance leaking more than 10 percent annually must be repaired and the repair verified within 30 days, or a retrofit or retirement plan started. A typical residential split system sits under both. What is never outside it is the venting prohibition — knowingly releasing refrigerant while servicing an appliance is prohibited under 40 CFR 82.154(a) at any charge size.

Those document a system that is working. This one isolates a fault on a system that is not. A start-up report proves you commissioned new equipment correctly; a maintenance checklist proves you serviced it on schedule. A diagnostic checklist starts from a customer complaint and works backwards through readings until the cause is named — which is why this form opens with the complaint, scopes its checks to that complaint, and ends with a root-cause box tied to the readings above it.

No. It is the technician’s record of a diagnostic visit — the complaint, the readings, and the conclusion drawn from them — and every export says so. The code and regulation references appear to explain why something was checked or what obligation attaches to it, not to certify anything. Approval of any work rests with the authority having jurisdiction.

Your diagnostic form does the refrigeration math. Larry answers the phone while it does.

We will run your numbers on the call and tell you if the maths does not work for a shop your size. That happens, and it is a cheaper conversation than finding out three months in.

Get a demo