Calculator
Standby Generator Sizing Calculator
Build the list of circuits that have to stay alive during an outage and get the standby generator that covers them, total running watts, the peak when the biggest motor starts last, required kW and kVA at the set’s power factor, the next standard genset rating, and the transfer switch amps. Free, no signup.
| Load | Qty | RunningSteady-state watts for one unit. For a motor row this becomes the NEC table full-load amps at your voltage. | SurgeStarting watts ÷ running watts for one unit. 1× is resistive (heat, lights). Motor rows use the NEC 430.7(B) locked-rotor code letter instead. | Remove |
|---|---|---|---|---|
11.7 kW peak starting · 6.99 kW running · air-cooled class
- Running: 6,990 W
- Starting surge: 4,712 W
- Spare capacity: 4,298 W
| Load | Running | Starting |
|---|---|---|
| Central A/C, 3 ton8,512 W starting (2.24×) | 3,800 W | +4,712 W |
| Refrigerator / freezer1,200 W starting (6×) | 200 W | +1,000 W |
| Furnace blower, ½ HP2,352 W starting (2.94×) | 800 W | +1,552 W |
| Sump pump, ⅓ HP1,304 W starting (1.63×) | 800 W | +504 W |
| LED bulb (each) × 15Resistive, no inrush | 150 W | - |
| Wi-Fi router + modemResistive, no inrush | 40 W | - |
| TV, 55" LEDResistive, no inrush | 200 W | - |
| MicrowaveResistive, no inrush | 1,000 W | - |
Starting is the extra draw when that one unit kicks in on top of everything already running. Only the single largest value is added to the peak, motors are assumed not to start simultaneously.
- Essential circuits only7.5-12 kWFridge, furnace blower, sump/well pump, lights and outlets.
- Most 2,000 sq ft homes14-22 kWEssentials plus one central A/C and a kitchen. Air-cooled.
- Large home, everything on22-48 kWTwo A/C systems, electric water heat, range, dryer. Liquid-cooled above 26 kW.
- Motor inrush across the line5-7× FLANEC 430.7(B) code letters F-H (5.0-7.09 locked-rotor kVA/HP) for Design B motors.
Surge multipliers and the sizing margin are manufacturer-practice heuristics, not NEC requirements. NEC Article 702 covers optional standby systems, 702.4(B) covers load management, and 220.87 lets an existing building be sized from a year of maximum-demand data. Confirm the final model with the manufacturer's sizing software and the AHJ.
List the loads that run at once
Start from a backup scope, essential circuits, essentials plus central A/C, or whole home, then add, remove, or edit rows. Each load carries published running watts and a starting (surge) multiplier, or you can size a motor straight from horsepower and its NEC locked-rotor code letter.
See running vs peak starting demand
The tool adds up every running watt, then adds the single largest starting surge on top, the largest motor started last. Only one motor is assumed to start at a time, so the answer never depends on the order of your list.
Get the set, the kVA, and the switch
Apply a sizing margin and read off the recommended standard standby kW rating, the required kVA at your power factor, the transfer switch ampere size, and how much spare capacity is left over the continuous load.
How it works
- 1
List the loads that run at once
Start from a backup scope, essential circuits, essentials plus central A/C, or whole home, then add, remove, or edit rows. Each load carries published running watts and a starting (surge) multiplier, or you can size a motor straight from horsepower and its NEC locked-rotor code letter.
- 2
See running vs peak starting demand
The tool adds up every running watt, then adds the single largest starting surge on top, the largest motor started last. Only one motor is assumed to start at a time, so the answer never depends on the order of your list.
- 3
Get the set, the kVA, and the switch
Apply a sizing margin and read off the recommended standard standby kW rating, the required kVA at your power factor, the transfer switch ampere size, and how much spare capacity is left over the continuous load.
Running watts vs starting watts, why generators get undersized
A generator has two limits, and only one of them is on the sticker. The rated (running) kW is the continuous power it will make all night. The surge capability is the much larger, very brief output it can hold while a motor pulls locked-rotor current. An across-the-line induction motor draws roughly five to seven times its full-load amps at the instant it starts, that is exactly what NEC Table 430.7(B) code letters F through H describe, at 5.0 to 7.09 locked-rotor kVA per horsepower. Size a set on running watts alone and the well pump or the A/C condenser will drop the voltage far enough to stall the motor, trip the breaker, or shut the set down. The standard fix is the "largest motor started last" method: add every running watt, then add the biggest single starting surge on top, because motors do not all start at the same moment.
This calculator runs that method end to end. It totals running watts across your load list, finds the largest starting delta, applies a sizing margin, and rounds up to the next standard standby rating from 7.5 kW air-cooled through 150 kW liquid-cooled. It reports both kW and kVA, kVA = kW ÷ power factor, and single-phase air-cooled home standby sets are rated at 1.0 power factor while three-phase standby sets are rated at 0.8, plus the transfer switch amps and the spare capacity left over your continuous load. Motor rows read full-load amps straight from NEC Tables 430.248 and 430.250 and locked-rotor kVA from Table 430.7(B). If a load-management module will shed circuits, tick them and the set is sized to what actually runs together, the allowance NEC 702.4(B) makes for optional standby systems.
Related tools
More free resources to help you price jobs, stay organized, and capture leads.
Business Templates
Free invoices, estimates, and work orders for your trade.
Browse templatesAI Receptionist
Let Crew answer every call while you focus on the job.
Learn moreContractor Blog
Guides on pricing, hiring, marketing, and operations.
Read guidesElectrical Licensing
State licensing requirements, exams, and renewal rules for electrical contractors.
View statesGenerator Sizing Calculator FAQs
Watch the work before you hear from us
Diagnostics, installs and the odd bad attic, from contractors who film their own jobs.