Calculator
Electrical Conduit Fill Calculator
Verify raceway fill before you pull, choose conduit type and trade size, add a row per conductor size and insulation, and get the fill percentage checked against the NEC Chapter 9 Table 1 limit, plus the smallest trade size that holds the bundle. Free, no signup.
| Insulation | Size | Qty | Area | Remove |
|---|---|---|---|---|
| 0.1197 | ||||
| 0.0211 |
NEC Chapter 9, Note 4: a conduit or tubing nipple no longer than 24 in., not including connectors, run between boxes, cabinets, or similar enclosures may be filled to 60%, and the 310.15(C)(1) bundling adjustment does not apply.
Conduit fill
26.4%
10 conductors · 0.1408 in² of 0.533 in² interior area
| Trade size | Fill | Allowed (40%) | Status |
|---|---|---|---|
| 1/2" | 46.3% | 0.122 | Over |
| 3/4"selected | 26.4% | 0.213 | Passesminimum |
| 1" | 16.3% | 0.346 | Passes |
| 1-1/4" | 9.4% | 0.598 | Passes |
| 1-1/2" | 6.9% | 0.814 | Passes |
| 2" | 4.2% | 1.342 | Passes |
| 2-1/2" | 2.4% | 2.343 | Passes |
| 3" | 1.6% | 3.538 | Passes |
| 3-1/2" | 1.2% | 4.618 | Passes |
| 4" | 1.0% | 5.901 | Passes |
- Equipment grounding and bonding conductors count toward fill (NEC Ch. 9, Note 3), add them as their own row. Note 3 requires their actual dimensions, insulated or bare.
- 1 conductor53%NEC Ch. 9 Table 1, a lone conductor may occupy 53% of the raceway.
- 2 conductors31%Two conductors bind against each other, so Table 1 drops the limit to 31%.
- 3 or more40%The everyday number, almost every real pull lands on the 40% column.
- Nipple ≤ 24 in.60%Note 4: short nipples between enclosures may be filled to 60%.
Pick the raceway
Choose conduit type, EMT, ENT, FMC, IMC, LFNC-A/B, LFMC, RMC, PVC Schedule 40 or 80, and trade size. Interior areas come straight from NEC Chapter 9 Table 4.
Add every conductor
Add a row per insulation type and AWG/kcmil size with a quantity, including the equipment grounding conductor, which NEC Chapter 9 Note 3 requires you to count. Areas come from Table 5.
Read the fill and the next size up
Get fill percentage with PASS or FAIL against the applicable 53%, 31%, 40% or 60% nipple limit, total conductor area, allowed fill area, remaining capacity in square inches, and a table comparing every trade size for that raceway.
How it works
- 1
Pick the raceway
Choose conduit type, EMT, ENT, FMC, IMC, LFNC-A/B, LFMC, RMC, PVC Schedule 40 or 80, and trade size. Interior areas come straight from NEC Chapter 9 Table 4.
- 2
Add every conductor
Add a row per insulation type and AWG/kcmil size with a quantity, including the equipment grounding conductor, which NEC Chapter 9 Note 3 requires you to count. Areas come from Table 5.
- 3
Read the fill and the next size up
Get fill percentage with PASS or FAIL against the applicable 53%, 31%, 40% or 60% nipple limit, total conductor area, allowed fill area, remaining capacity in square inches, and a table comparing every trade size for that raceway.
How the NEC decides how many wires fit in a conduit
Conduit fill is a cross-sectional area problem, not a wire count. NEC Chapter 9 Table 1 caps how much of a raceway’s interior the conductors may occupy: 53% for a single conductor, 31% for exactly two, and 40% for three or more. The two-conductor case is the strictest because two round conductors bind against each other in a bend, which is why adding a third conductor can make a pull legal that two would not be. A conduit or tubing nipple no longer than 24 inches between boxes or cabinets is permitted 60% fill under Note 4, and the 310.15(C)(1) bundling adjustment does not apply to it.
This calculator implements the full Chapter 9 chain: Table 4 interior areas for ten raceway types from 3/8 inch to 6 inch, Table 5 conductor areas for THHN/THWN-2, XHHW/XHHW-2, TW/THW/THHW/THW-2 and both RHH/RHW variants from 14 AWG to 1000 kcmil, and Note 7 rounding, where all conductors are the same size, a calculated decimal of 0.8 or larger rounds up to the next whole conductor. That last rule is where most online fill calculators go wrong: it means an all-same-size pull can sit slightly past the raw area limit and still be code-compliant, which is exactly how NEC Annex C arrives at its published counts. This tool reproduces 1,424 Annex C rows across EMT, IMC, RMC and PVC Schedule 40 and 80.
Related tools
More free resources to help you price jobs, stay organized, and capture leads.
Business Templates
Free invoices, estimates, and work orders for your trade.
Browse templatesAI Receptionist
Let Crew answer every call while you focus on the job.
Learn moreContractor Blog
Guides on pricing, hiring, marketing, and operations.
Read guidesElectrical Licensing
State licensing requirements, exams, and renewal rules for electrical contractors.
View statesConduit Fill Calculator FAQs
Watch the work before you hear from us
Diagnostics, installs and the odd bad attic, from contractors who film their own jobs.